ID 70547
Movement to fixed stop aborted from follow-up operation. | |||
Description | Tracking mode was activated during an active Move to fixed stop function [FCT-M8]. The approach motion is aborted and clamping of the fixed stop that has already taken place cannot be maintained. | ||
Response | Class | 6 | Controlled halt of the axis, the control loop is closed. Transition to error state. The Move to fixed stop function is terminated. |
Solution | Class | 6 | Check and modify the sequences in the NC program and the PLC. |
Parameter | %1 | Logical axis number [-] | |
Logical axis number P-AXIS-00016 of axis affected. | |||
%2 | Current value [-] | ||
Fixed stop already detected | |||
Error type | - | ||
| |||