ID 110488
Changing the operation mode "gantry slave axis" requires restart of the control. | ||||
Description | The operation of an axis as "slave axis of a gantry link" (see P-AXIS-00015) may not be changed while the CNC kernel is running. The new value is not adopted; the old setting remains valid. | |||
Response | Class | 0 | Warning and correct parameter P-AXIS-00015 | |
Solution | Class | 0 | Only change the operation mode “slave axis of gantry link“ in configuration mode or if the CNC is not running. | |
Parameter | %1: |
| ||
Logical axis number P-AXIS-00016 of axis affected | ||||
%2: |
| |||
Current axis operation mode P-AXIS-00015 | ||||
%3: |
| |||
Corrected P-AXIS-00015 operation mode of the axis. | ||||
Error type | - | |||
| ||||