ID 110417
Invalid value for parameter probing_input_number was corrected. | ||||
Description | The axis was set as probing axis (P-AXIS-00118) and an invalid value was specified for the probing input to be used at the drive (parameter P-AXIS-00295). | |||
Response | Class | 1 | Warning output, correct value of P-AXIS-00295 to 1. | |
Solution | Class | 1 | In the axis parameter list, assign a valid value (1 or 2) to parameter P-AXIS-00295. In the drive, the latch function must be assigned to the digital input used by assigning the value 26 to drive parameter IN1MODE or IN2MODE. | |
Parameter | %1: | Logical axis number [-] | ||
Logical axis number of affected axis (see P-AXIS-00016). | ||||
%2: | Incorrect value [-] | |||
| ||||
%3: | Lower limit value [-] | |||
| ||||
%4: | Upper limit value [-] | |||
| ||||
%5: | Corrected value [-] | |||
| ||||
Error type | 2, Error message by data transfer from parameter list into control device. | |||
| ||||