ID 90165
Multipath programming not active when tool radius compensation is active. | |||
Description | A NC program was started with TRC in 2 paths.
The following parameters must be set in order to use TRC in 2 paths:
Correct Channel parameter list: multi_path_configuration 1 # P-CHAN-00261
Activate the function: configuration.tool_radius_comp.function MULTI_PATH # P-CHAN-00555
Alternatively, the function can be activated in the start-up list. configuration.channel[0].tool_radius_comp.function MULTI_PATH # P-STUP-00080
Wrong: configuration.tool_radius_comp.function 0
or in the start-up list configuration.channel[0].tool_radius_comp.function 0
| ||
Response | Class | 2 | Abort NC program processing. |
Solution | Class | 6 | Activate the function P-CHAN-00555 (or P-STUP-00080) |
Error type | 1, Error message from NC program. | ||
| |||