ID 70385
The configured maximum value is less than the configured minimum value. | ||||
Description | The parametrised minimum value (P-AXIS-00408) is greater than the parametrised maximum value (P-AXIS-00409). | |||
Response | Class | 1 | Warning output, P-AXIS-00408 and P-AXIS-00409 are swapped. | |
Solution | Class | 1 | P-AXIS-00408 and P-AXIS-00409 must be adjusted. | |
Parameter | %1: | Logical axis number [-] | ||
| ||||
%2: | Current value [-] | |||
Value of P-AXIS-00396 for identification of drive function. | ||||
%3: | Upper limit value [-] | |||
Parameterized value of P-AXIS-00409. | ||||
%4: | Lower limit value [-] | |||
Parameterized value of P-AXIS-00408. | ||||
Error type | 11, Error message from position controller. | |||
| ||||