ID 70377
The actual value simulation was activated when speed monitoring was active. | ||||
Description | Simulation of actual value positions was activated with active spindle speed monitoring. The actual value simulation is activated when the current spindle speed is higher than the maximum encoder velocity set in P-AXIS-00220. When the encoder velocity limit is exceeded, it is assumed that the encoder does not deliver valid actual values any more; monitoring the spindle speed is not possible in this case. | |||
Response | Class | 7 | Program abort | |
Solution | Class | 6 | Increase P-AXIS-00220 or reduce the maximum spindle speed. | |
Parameter | %1: | Logical axis number [-] | ||
| ||||
%2: | Error value [-] | |||
| ||||
Error type | 11, Error message from position controller. | |||
| ||||