ID 70318
Activation of cross compensation not possible since master axis is not referenced. | ||||
Description | The master axis for cross compensation must be homed in order to activate compensation. The correction values for the slave axis are calculated depending on the position of the master axis. See [FCT-C5// Section: Cross compensation] | |||
Response | Class | 1 | Warning, cross compensation remains inactive until master axis is homed | |
Solution | Class | 1 | Home the master axis (see [FCT-M1]) If an absolute path measurement system is used for the master axis, parameter P-AXIS-00014 can be set to 1 for the master axis to mark homing of the axis. | |
Parameter | %1: | Logical axis number [-] | ||
Logical axis number P-AXIS-00016 of slave axis affected | ||||
%2: | Logical axis number [-] | |||
Logical axis number P-COMP-00005 of master axis | ||||
%3: | Error value [-] | |||
TRUE if axis is homed | ||||
Error type | 11, Error message from position controller. | |||
| ||||