ID 70245
The command positions for cross compensation are not sorted in an ascending order. | ||||
Description | Compensation values are specified for cross compensation in the compensation value lists at defined interpolation points. between Between these points, the correction values are determined using linear interpolation. Therefore they must be arranged according to their position in an ascending order. A possible error cause can be using less interpolation points than the number given in the parameter P-COMP-00004 since the positions of the unused points are set to zero (nil). [FCT-C5//Section: Cross compensation]) [COMP// Section: Cross compensation])
Wrong example (extract from compensation data list) kw.crosscomp.table[0].sollw 0 kw.crosscomp.table[0].correction 0 kw.crosscomp.table[1].sollw 100000 kw.crosscomp.table[1].correction 1000 kw.crosscomp.table[2].sollw 300000 kw.crosscomp.table[2].correction 3000 kw.crosscomp.table[3].sollw 200000 kw.crosscomp.table[3].correction 2000
Corrected example (extract from compensation data list) kw.crosscomp.table[0].sollw 0 kw.crosscomp.table[0].correction 0 kw.crosscomp.table[1].sollw 100000 kw.crosscomp.table[1].correction 1000 kw.crosscomp.table[2].sollw 200000 kw.crosscomp.table[2].correction 2000 kw.crosscomp.table[3].sollw 300000 kw.crosscomp.table[3].correction 3000
| |||
Response | Class | 7 | Closed-loop controlled axis stop and disabling of cross compensation | |
Solution | Class | 7 | Correct compensation value table see P-COMP-00006 | |
Parameter | %1: | Logical axis number [-] | ||
Logical axis number (P-AXIS-00016) of concerned axis | ||||
%2: | Current value [-] | |||
Position of last interpolation point see P-COMP-00006 | ||||
%3: | Error value [-] | |||
Position of current interpolation point see P-COMP-00006 | ||||
%4: | Current value [-] | |||
Index of actual interpolation point | ||||
Error type | 2, Error message by data transfer from parameter list into control device. | |||
| ||||