ID 70244
No compensation value list available for cross compensation. | ||||
Description | An axis in the the axis parameters is selected for cross compensation (sag compensation) (P-AXIS-00047). However, the compensation value list containing the required correction values is missing (see [COMP// Section: Cross compensation]) [FCT-C5//Cross compensation] | |||
Response | Class | 7 | Closed-loop controlled axis stop and disable cross compensation | |
Solution | Class | 7 | If cross compensation is enabled for an axis, a compensation value list must also be specified for it in the start-up list P-STUP-00016, P-STUP-00017, P-STUP-00036) (see [COMP// Section: Cross compensation]).
Example (extract from start-up list):
zahl_kw 1 achs_kw[0] ..\listen\achskw3.lis achs_kw_log_ax_nr[0] 3 | |
Parameter | %1: | Logical axis number [-] | ||
Logical axis number of affected axis see P-AXIS-00016 | ||||
Error type | 11, Error message from position controller. | |||
|