ID 44005
FB error: acceleration exceeds allowed range. | |||
Description | With FBs MC_MoveAbsolute, MC_MoveAdditive, MC_MoveRelative, MC_MoveSuperImposed, MC_MoveVelocity, MC_GearIn and MC_Phasing the value at the input variable “Acceleration” is checked before a command is sent to the motion controller. This error message is output If the value exceeds the interval [1.0, 2147483647.0]. | ||
Response | Class | - | The job is discarded by the FB and not transferred to the motion controller. |
Solution | Class | - | Adjust the value at input “Acceleration” so that it lies within the limits of the permitted interval. Afterwards, the FB can be reassigned. |
Error type | - | ||
| |||