ID 44002
FB error: order isn't acknowledged within a defined number of PLC cycles. | |||
Description | After a defined number (MAX_RESET_WAIT_CYCLES) of PLC cycles, the job is still active and the function block did not receive the acknowledge information for that job. | ||
Response | Class | - | The "Error" and "ErrorID" outputs of the function block indicate the error situation. Function block switches to its idle state and is able to command a new job in the next PLC cycle. |
Solution | Class | - | Check whether the motion controller is still running and calls its tasks cyclically. If the motion controller fails to run, restart the control system, otherwise contact your control system supplier. |
Error type | - | ||
| |||