ID 21469
Unexpected UNTIL. Does not match the current control block. | |||
Description | A control block statement was programmed in incomplete syntax. A $UNTIL can only be programmed in combination with a previous $REPEAT. Example: Wrong:
N10 G00 X0 Y0 Z0 P1=1 N20 $UNTIL P1>2 : N1000 M30
Correct:
N10 G00 X0 Y0 Z0 P1=1 N15 $REPEAT : N20 $UNTIL P1>2 : N1000 M30 | ||
Response | Class | 2 | Abort NC program processing. |
Solution | Class | 3 | Check and modify the program flow sequence. Insert the $REPEAT instruction or delete the $UNTIL. |
Error type | 1, Error message from NC program. | ||
|