ID 21389
Parameterization not permitted when OTC is active. | |||
Description | The parameterization of the OTC function (Online Tool Compensation) may only take place before or simultaneously with the selection #OTC ON [...]. If OTC is already active, do not change the parameter settings any more. Example: Wrong:
N05 G01 X100
N10 #OTC ON
N15 #OTC [LENGTH CONT WEAR_CONST_TOOL]
or
N10 #OTC ON [LENGTH CONT WEAR_CONST_TOOL]
N15 #OTC [LENGTH AUTO WEAR_CONST_TOOL]
N20 G01 X200
:
N900 #OTC OFF
N1000 M30
Correct:
N05 G01 X100
:
N10 #OTC [LENGTH CONT WEAR_CONST_TOOL]
N15 #OTC ON
or
N10 #OTC ON [LENGTH CONT WEAR_CONST_TOOL]
:
N20 G01 X200
:
N900 #OTC OFF
N1000 M30
| ||
Response | Class | 2 | Abort NC program processing. |
Solution | Class | 3 | Check and modify NC program. Adapt the sequence of parameterisation and selection of OTC. |
Error type | 1, Error message from NC program. | ||
| |||