ID 21369
PDU received from tool management with invalid parameter index. | ||||
Description | A transparent read access with V.G.WZ[j].GOBJECT[i].* to certain tool object data in an external tool database results in the NC channel receiving an object data record with an invalid index. The highest index may have a maximum value of 4 with a maximum of 5 permissible object data records. | |||
Response | Class | 2 | Abort NC program processing. | |
Solution | Class | 6 | Check internal processes in the external tool database (e.g. PLC) during transparent read access. The maximum index in the object data set to be provided must be in the range 0 - 4. | |
Parameter | %1: | Error value [-] | ||
| ||||
%2: | Lower limit value [-] | |||
| ||||
%3: | Upper limit value [-] | |||
| ||||
Error type | 1, Error message from NC program. | |||
| ||||