ID 21348
Helical interpolation with slope not permissible without 3rd dimension. | ||||
Description | Helical interpolation is the superposition of a circular interpolation (plane of 1st and 2nd main axis) and a linear motion in the 3rd main axis. The message is generated if the position specified in the 3rd main axis (“Z axis”) is missing when helical motion is programmed. Example: Wrong:
N10 G17 G90 X-10 Y0 Z0 F500 G161
N20 G03 I0 J0 K10
:
N1000 M30
Correct:
N10 G17 G90 X-10 Y0 Z0 F500 G161
N20 G03 I0 J0 Z50 K10 (helical movement with 5 windings)
:
N1000 M30
| |||
Response | Class | 1 | Abort NC program processing. | |
Solution | Class | 3 | Check and modify NC program. Supplement the position in the 3rd main axis (“Z axis”) for helical motion. | |
Parameter | %1: | Initial value [0.1 µm or 0.0001°] | ||
Start position of the 3rd main axis | ||||
%2: | Final value [0.1 µm or 0.0001°] | |||
End position of the 3rd main axis | ||||
Error type | 1, Error message from NC program. | |||
| ||||