ID 21304
Channel parameters: SLOPE parameter is out of range of permissible values. | ||||
Description | One of the default slope parameters specified in the channel parameters (P-CHAN-00071, P-CHAN-00073, P-CHAN-00001) exceeds the permissible numerical range. | |||
Response | Class | 1 | Controller start-up is continued. | |
Solution | Class | 1 | Check and modify the corresponding default slope parameter in the channel parameters before the next controller start-up. In case of conflict, the invalid default slope parameter is set to zero (nil) at start-up and the start-up is continued. | |
Parameter | %1: | Error value [-] | ||
| ||||
%2: | Lower limit value [-] | |||
| ||||
%3: | Upper limit value [-] | |||
| ||||
%4: | Corrected value [-] | |||
| ||||
Error type | 2, Error message by data transfer from parameter list into control device. | |||
| ||||