ID 20707
Program paths of the same type are not allowed to have the same priority. | ||||
Description | The start-up list contains configured program paths that may be of the same type as P-STUP-00020 but may not have the same priority asP-STUP-00021.
Example with error: pfad[0].prg[0] v:\ref_test\nc_prg\init pfad[0].log_nr[0] 1 pfad[0].typ[0] 0x03 pfad[0].prioritaet[0] 1 # pfad[0].prg[1] v:\ref_test\nc_prg\dec pfad[0].log_nr[1] 1 pfad[0].typ[1] 0x03 pfad[0].prioritaet[1] 1 | |||
Response | Class | 2 | Controller start-up is aborted. | |
Solution | Class | 6 | Check and modify the priority settings for program paths in the start-up list. Repeat the NC start-up. | |
Parameter | %1: | Error value [-] | ||
Invalid priority P-STUP-00021 | ||||
%2: | Current value [-] | |||
Program path type P-STUP-00020 | ||||
Error type | - | |||
| ||||