ID 20651
NC command is not allowed during active TRC. | |||
Description | With active tool radius compensation (G41/G42) no function selection or deselection is possible which leads to flushing of CNC channel. These are, for example, the following CNC commands / functions:
The Exception list of commands with active TRC/SRK lists the commands that are not permitted. | ||
Response | Class | 2 | Abort NC program processing. |
Solution | Class | 3 | Deselect tool radius compensation with G40 before using NC commands that result in flushing of the CNC channel. |
Error type | 1, Error message from NC program. | ||
| |||