ID 20569
In NC block #COMMENT END has to be programmed exclusively. | |||
Description | After the #COMMENT END command, no further NC commands are permitted in the same NC block. Example: Wrong:
N10 #COMMENT BEGIN
:
N30 #COMMENT END X100 F1000 G01 F100
:
N1000 M30
Correct:
N10 #COMMENT BEGIN
:
N30 #COMMENT END
N40 X100 F1000 G01 F100
:
N1000 M30
For further information see [PROG// Section: Cross-block comments] | ||
Response | Class | 2 | Abort NC program processing. |
Solution | Class | 3 | Check and adjust NC program sequence. Move the invalid NC commands to the following NC block. Note: Further NC commands are only permitted in the same NC block with #ACHSE, #PSET and #PRESET. |
Error type | 1, Error message from NC program. | ||
| |||