ID 20244
Unexpected *CONTINUE’. No valid/open control blocks. | |||
Description | A control block statement was programmed in incomplete syntax. A $CONTINUE can only be programmed inside any loop or $SWITCH statement. Example: Wrong: N10 G00 X0 Y0 Z0 N20 $CONTINUE : N1000 M30 Correct: N10 G00 X0 Y0 Z0 P1=1 N20 $DO N30 P1=P1+1 N40 $IF P1 == 2 N50 $CONTINUE N60 $ENDIF : N100 $ENDDO P1 < 10 : N1000 M30 For further information see
| ||
Response | Class | 2 | Abort NC program processing. |
Solution | Class | 3 | Check and modify the program flow sequence. Insert a loop or $SWITCH statement or remove the $CONTINUE command. |
Error type | 1, Error message from NC program. | ||
| |||