ID 20242

'BREAK' must be programmed exclusively in NC-block.

Description

In the same NC block, a control block instruction was programmed with further NC commands. After a $BREAK no further NC commands may be programmed.

Example:

Wrong:
N10   G00 X0 Y0 Z0
N20   P1=5
N30   $SWITCH P1
N60     $CASE 5
N70     G01 X100 F10000
N80     $BREAK G01 Y200 F10000
N90   $DEFAULT
N100    P1=0
N110    $BREAK
N120  $ENDSWITCH
:
N1000 M30
Correct:
N10   G00 X0 Y0 Z0
N20   P1=5
N30   $SWITCH P1
N60     $CASE 5
N70     G01 X100 F10000
N75     G01 Y200 F10000
N80     $BREAK
N90   $DEFAULT
N100    P1=0
N110    $BREAK
N120  $ENDSWITCH
:
N1000 M30

For further information see [PROG// Section: Switch branching]

Response

Class

2

Abort NC program processing.

Solution

Class

3

Check and modify NC program. Move the not permissible NC commands after $BREAK to other NC blocks or delete them.

Error type

1, Error message from NC program.