ID 20233
ENDFOR must be programmed exclusively in the block. | |||
Description | In the same NC block, a control block instruction was programmed with further NC commands. After a $ENDFOR no further NC commands may be programmed. Example: Wrong:
N10 G00 X0 Y0 Z0
N20 $FOR P1=1, 10, 2
:
N30 $ENDFOR G01 X100 F10000
:
N1000 M30
Correct:
N10 G00 X0 Y0 Z0
N20 $FOR P1=1, 10, 2
:
N30 $ENDFOR
N40 G01 X100 F10000
:
N1000 M30
For further information see [PROG// Section: Counting loop] | ||
Response | Class | 2 | Abort NC program processing. |
Solution | Class | 3 | Check and modify NC program. Move the not permissible NC commands after $ENDFOR to other NC blocks or delete them. |
Error type | 1, Error message from NC program. | ||
| |||