ID 20206
$ command must be programmed exclusively in NC block. | |||
Description | A control block sequence starting with the dollar character $ is programmed with other NC commands in the same NC block. Example: Wrong:
N10 G00 X0 Y0 Z0
N20 $FOR P10=0, 20, 1 G01 X10 F100
N30 G91 X5
N40 $ENDFOR
:
N1000 M30
Correct:
N10 G00 X0 Y0 Z0
N15 G01 X10 F100
N20 $FOR P10=0, 20, 1
N30 G91 X5
N40 $ENDFOR
:
N1000 M30
| ||
Response | Class | 2 | Abort NC program processing. |
Solution | Class | 3 | Check and modify NC program. Program the control block sequence and the other NC commands in separate NC blocks. |
Error type | 1, Error message from NC program. | ||
| |||