ID 20133

Plane selection not allowed during active tool radius compensation.

Description

As long as the tool radius compensation is enabled, it is not permitted to program a plane selection via G17, G18 or G19.

Example:

Wrong:
N10   G00 X0 Y0 Z0
N20   G41
N30   G19
N1000 M30
Correct:
N10   G00 X0 Y0 Z0
N20   G41
:
N25   G40
N30   G19
N35   G41
:
N999  G40

N1000 M30

Response

Class

2

Abort NC program processing.

Solution

Class

3

Check and modify the NC program sequence. Deselect the TRC with G40 before programming plane selection.

Parameter

%1:

Error value [-]

Invalid G function

Error type

1, Error message from NC program.