ID 20054
Corrected centre point is out of data format. | ||||
Description | The values chosen for start / end point and radius imply centre coordinates that are outside the permissible numerical range. Example: Wrong: N10 G00 X0 Y0 Z0 N20 G02 X1 R1000000 F1000 N1000 M30 Correct: N10 G00 X0 Y0 Z0 N20 G02 X1 R0.5 F1000
| |||
Response | Class | 2 | Abort NC program processing. . | |
Solution | Class | 3 | Check and modify NC program. Change the value of the radius. | |
Parameter | %1: | Logical axis number [-] | ||
Axis with exceeded data range | ||||
%2: | Upper limit value [-] | |||
| ||||
%3: | Lower limit value [-] | |||
| ||||
%4: | Error value [-] | |||
| ||||
Error type | 1, Error message from NC program. | |||
| ||||