ID 13121
Spindle speed not defined. | |||
Description | For thread tapping, the spindle speed must be specified to calculate the feed rate. This message is generated if the spindle speed is neither programmed in the input parameters nor pre-assigned in the tool parameters. (See section: Cyclic-specific tool data). | ||
Response | Class | - | Error: Transition to error state. Complete reset of the NC channel necessary. |
Solution | Class | - | Check and define the spindle position and correct the input or tool parameters. If both are assigned, the spindle position from the input parameters is used. |
Error type | 1, Error message from the NC program | ||
| |||