Time delay filter

The time delay filter is available in each of the CNC Builds as of

V2.11.2013, V2.11.2803 and V3.00.3013.

Response

A signal can be delayed by the time delay filter. The amplitude response of this filter is constant 1, i.e. the signal profile does not change One application, for example, is to compensate for dead times in the drive train, if this is not identical in all axes. The filter delay time must be within the interval 0 ≤ delay time (filter[i].time_constant) < 6 * cycle time of the NC controller.

The filter is parameterised by defined the required filter time constant (filter[i].time_constant). It is not necessary to specify a filter prototype of a cut-off frequency for the time delay filter. To activate the filter, a filter order must also be specified > 0 (filter[i].order). However, the order is recalculated in the CNC when the filter coefficients are generated depending on the delay time settings.

Time delay filter 1:
Signal profiles of the time delay filter

The figure shows the signal profiles of the time delay filter with different time constants (filter[i].time_constant).

Example

Axis filters: Time delay filter with time constant of 0.002 seconds:

filter[0].enable

1

filter[0].order

1

filter[0].type

TIME_DELAY

filter[0].time_constant

2000

filter[0].share_percent

100

Example

Additional interface: Time delay filter with time constant of 0.002 seconds

lr_param.add_interface.enable

1

lr_param.add_interface.filter[0].enable

1

lr_param.add_interface.filter[0].order

1

lr_param.add_interface.filter[0].type

TIME_DELAY

lr_param.add_interface.filter[0].time_constant

2000

lr_param.add_interface.filter[0].share_percent

100