Description

Axis parameter

P-AXIS-00789

Activate crosstalk compensation

Description

This parameter activates the crosstalk compensation function.

Parameter

lr_param.crosstalk

Data type

BOOLEAN

Data range

0/1

Axis types

T

Dimension

T: ----

 

Default value

0

Drive types

 

Remarks

Parameter available as of CNC Build V3.1.3079.32 and higher

Compensation parameters

P-COMP-00063

Logical axis number of the master axis

Description

This parameter determines the logical number of the master axis whose acceleration is used as the input variable of the compensation value list of the slave axis.

Parameter

kw.crosstalk.master_dyn_ax_nr

Data type

UNS16

Data range

1 ≤ P-COMP-00063 ≤ MAX (UNS16)

Axis types

T

Dimension

T: ----

R,S: -

Default value

0

Remarks

Parameter available as of CNC Build V3.1.3081.2 or V3.1.3108.4.

P-COMP-00064

Number of cycles for ‘smooth switching’

Description

This parameter determines the number of cycles for which crosstalk compensation is coupled/decoupled softly.

Parameter

kw.crosstalk.n_cycles

Data type

UNS16

Data range

0 ≤ P-COMP-00064 ≤ 20 (maximum number of cycles above which coupling or decoupling is to occur)

Axis types

T, R, S

Dimension

T: ----

R, S: -

Default value

0

Remarks

Parameter available as of CNC Build V3.1.3079.32

P-COMP-00066

Accelerations of the master axis

Description

This parameter defines the acceleration of the master axis requiring a compensation of the slave axis.

Parameter

kw.crosstalk.acceleration

Data type

REAL64

Data range

0 < P-COMP-00066 < MAX(SGN64-1023)

Axis types

T

Dimension

T: [mm/s²]

R,S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

As of V3.1.3132.0 and/or V4.29.0, the data type is REAL64; in earlier versions SGN32. This also affects the related data range.

P-COMP-00067

Negative acceleration of the master axis

Description

This parameter defines the negative acceleration of the master axis which must be used to compensate the slave axis.

Parameter

kw.crosstalk.deceleration

Data type

REAL64

Data range

MIN(SGN64-1023) ≤ P-COMP-00067 < 0

Axis types

T

Dimension

T: [mm/s²]

R,S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

As of V3.1.3132.0 and/or V4.29.0, the data type is REAL64; in earlier versions SGN32. This also affects the related data range.

P-COMP-00065

Manual activation of crosstalk compensation

Description

The CNC activates crosstalk compensation automatically if it is selected in the axis parameters (P-AXIS-00789) and the required preconditions are met.

If the parameter P-COMP-00065 is set to 1, crosstalk compensation must be explicitly activated by an NC command.
[PROG// Selecting/deselecting axis compensations in the NC program (COMP)]

Compensation is deactivated at the end of the NC program, when the CNC is reset or when the compensating axis is released.

Parameter

kw.crosstalk.manual_activation

Data type

BOOLEAN

Data range

0: Automatic activation

1: Explicit activation in NC program

Axis types

T

Dimension

T: ----

R, S: -

Default value

0

Remarks

Parameter available as of CNC Build V3.1.3081.2 or V3.1.3108.4.

P-COMP-00080

Logical axis number of the first adaptation axis

Description

This parameter defines the logical axis number of the first adaptation axis. The position of the adaptation axis influences compensation in Modes 2 and 3 (P-COMP-00082).

Parameter

kw.crosstalk.master_pos1_ax_nr

Data type

UNS16

Data range

0 < P-COMP-00080 < MAX(UNS16)

Axis types

T

Dimension

T: ----

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

P-COMP-00081

Logical axis number of the second adaptation axis

Description

This parameter defines the logical axis number of the second adaptation axis. The position of the adaptation axis influences compensation in Mode 3 (P-COMP-00082).

Parameter

kw.crosstalk.master_pos2_ax_nr

Data type

UNS16

Data range

0 < P-COMP-00081 < MAX(UNS16)

Axis types

T

Dimension

T: ----

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

P-COMP-00082

Crosstalk compensation mode

Description

This parameter specifies the compensation mode.

Parameter

kw.crosstalk.mode

Data type

UNS08

Data range

1 …3

Axis types

T

Dimension

T: ----

R, S: -

Default value

1

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

P-COMP-00083

Number of measurement tests in the compensation value list

Description

This parameter sets the number of measurement tests specified in the compensation value list.

Parameter

kw.crosstalk.max_points

Data type

UNS32

Data range

0 ≤ P-COMP-00083 < 15

Axis types

T

Dimension

T: ----

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

P-COMP-00084

Different compensation values for different motion directions

Description

This parameter sets whether a compensation should use different compensation values for different motion directions.

Parameter

kw.crosstalk.velocity_dependent

Data type

BOOLEAN

Data range

0 / 1

Axis types

T

Dimension

T: ----

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

P-COMP-00085

Position of the first adaptation axis with acceleration test

Description

This parameter specifies the position of the first adaptation axis for the ith acceleration test.

Parameter

kw.crosstalk.position[i].ax_1

Data type

SGN64

Data range

MIN(SGN64) ≤ P-COMP-00085 < MAX(SGN64)

Axis types

T

Dimension

T: [0.1 µm]

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

P-COMP-00086

Position of the second adaptation axis with acceleration test

Description

This parameter specifies the position of the second adaptation axis for the ith acceleration test.

Parameter

kw.crosstalk.position[i].ax_2

Data type

SGN64

Data range

MIN(SGN64) ≤ P-COMP-00086 < MAX(SGN64)

Axis types

T

Dimension

T: [0.1 µm]

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

P-COMP-00087

Compensation value for acceleration in positive motion direction

Description

Compensation value at position i for acceleration in positive motion direction.

Parameter

kw.crosstalk.position[i].correction_accelerate_dir_pos

Data type

SGN64

Data range

MIN(SGN64) ≤ P-COMP-00087 < MAX(SGN64)

Axis types

T

Dimension

T: [0.1 µm]

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

P-COMP-00088

Compensation value for acceleration in negative motion direction

Description

Compensation value at position i for acceleration in negative motion direction.

Parameter

kw.crosstalk.position[i].correction_accelerate_dir_neg

Data type

SGN64

Data range

MIN(SGN64) ≤ P-COMP-00088 < MAX(SGN64)

Axis types

T

Dimension

T: [0.1 µm]

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

This parameter is only active if P-COMP-00084 is activated.

P-COMP-00089

Compensation value for deceleration in positive motion direction

Description

Compensation value at position i for deceleration in positive motion direction.

Parameter

kw.crosstalk.position[i].correction_decelerate_dir_pos

Data type

This parameter is only active if P-COMP-00084 is activated.

Data range

MIN(SGN64) ≤ P-COMP-00089 < MAX(SGN64)

Axis types

T

Dimension

T: [0.1 µm]

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

P-COMP-00090

Compensation value for deceleration in negative motion direction

Description

Compensation value at position i for deceleration in negative motion direction.

Parameter

kw.crosstalk.position[i].correction_decelerate_dir_neg

Data type

SGN64

Data range

MIN(SGN64) ≤ P-COMP-00090 < MAX(SGN64)

Axis types

T

Dimension

T: [0.1 µm]

R, S: -

Default value

0

Remarks

Parameter available as of V3.1.3081.2 and V3.1.3108.4

This parameter is only active if P-COMP-00084 is activated.