Description

P-AXIS-00271

Selection of temperature compensation

Description

The parameter selects the temperature compensation.

Parameter

lr_param.temp_comp

Data type

BOOLEAN

Data range

0/1

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

Drive types

----

Remarks

 

P-AXIS-00272

Parameterisation of temperature compensation (Basic position)

Description

The compensation values are approximated by a linear straight line. This straight line is defined by a basic position, an offset at this position and a geometrical pitch. Depending on the temperature, these parameters can be adjusted e.g. by the PLC.

Parameter

lr_param.temp_comp_position_0

Data type

REAL64

Data range

MIN(SGN64-1023) < temp_comp_position_0 < MAX(SGN64-1023)

Axis types

T, R, S

Dimension

T: 0.1µm

R,S: 0.0001 °

Default value

0

Drive types

----

Remarks

As of V3.1.3132.0 and/or V4.29.0, the data type is REAL64; in earlier versions SGN32. This also affects the related data range.

P-AXIS-00273

Parameterisation of temperature compensation (Offset)

Description

The compensation values are approximated by a linear straight line. This straight line is defined by a basic position, an offset at this position and a geometrical pitch. Depending on the temperature, these parameters can be adjusted e.g. by the PLC.

Parameter

lr_param.temp_comp_offset_0

Data type

REAL64

Data range

MIN(SGN64-1023)< temp_comp_offset_0 < MAX(SGN64-1023)

Axis types

T, R, S

Dimension

T: 0.1µm

R,S: 0.0001 °

Default value

0

Drive types

----

Remarks

As of V3.1.3132.0 and/or V4.29.0, the data type is REAL64; in earlier versions SGN32. This also affects the related data range.

P-AXIS-00274

Parameterisation of temperature compensation (Geometrical pitch)

Description

The compensation values are approximated by a straight line. This straight line is defined by a basic position, an offset at this position and a geometrical pitch. Depending on the temperature these parameters can be adjusted e.g. by the PLC.

Parameter

lr_param.temp_comp_coefficient

Data type

REAL64

Data range

-10000 ≤ temp_comp_coefficient ≤ 10000

Axis types

T, R, S

Dimension

T: µm/m

R,S: ----

Default value

0

Drive types

----

Remarks

 

P-AXIS-00275

Distribution of the temperature compensation on several cycles

Description

The compensation values are recalculated for each interpolation cycle. If the change per cycle exceeds the given maximum axis acceleration, this change can be output filtered over multiple cycles.

For this the number of cycles of the sin² filter can be defined in the axis parameter list.

Parameter

lr_param.temp_comp_n_cycles

Data type

UNS16

Data range

0 < temp_comp_n_cycles < 20

Axis types

T, R, S

Dimension

T: Number of interpolation cycles

R,S: Number of interpolation cycles

Default value

0

Drive types

----

Remarks

 

P-AXIS-00482

Manual activation of the temperature compensation

Description

The CNC turns the temperature compensation on when it is selected in the axis parameter list (P-AXIS-00271) and the required preconditions are met (e.g. the axis is homed).

If the parameter is set to 1, the temperature compensation must be manually turned on in the NC program via an NC command (see [PROG//Switching axis compensation on/off in the NC program]). In addition, the compensation is turned off at the end of the NC program, during CNC reset and axis release.

Parameter

lr_param.temp_comp_manual_activation

Data type

BOOLEAN

Data range

0: Automatic activation (default).

1: Manual activation in NC program.

Axis types

T, R, S

Dimension

T: ----

R,S: ----

Default value

0

Drive types

----

Remarks