Reading diagnostic signals

Description

The function block KRC_Diag reads the diagnostic signals of the robot controller.

Reading diagnostic signals 1:

The function block may only be instanced once per axis group. In the case of multiple instancing, the signals of the most recently called function block are output.

Reading diagnostic signals 2:

Inputs

Parameter

Type

Description

AxisGroupIdx

INT

Index of axis group

  • 1 … 5

ShowTrace

BOOL

TRUE = activate display of the active function blocks in the message window of the iiQKA.OS2 user interface.

FALSE = deactivate display of the active function blocks in the message window of the iiQKA.OS2 user interface.

Notice: Only activate the display for test and diagnostic purposes. If the display is active, approximate positioning is no longer possible and the cycle time of the submit interpreter is adversely affected.

MaxSubmitCycle

INT

Maximum cycle time of the submit interpreter

Default: 1 000 ms

Notice: If the maximum cycle time is exceeded, the $MOVE_ENABLE signal for the motion enable is reset.

Outputs

Parameter

Type

Description

Valid

BOOL

TRUE = data are valid

QueueCount

INT

Number of buffered statements

  • 1 … 90

PosActValid

BOOL

TRUE = position data are valid (BCO)

BrakeActive

BOOL

TRUE = robot is stopped by means of a BRAKE statement

SubmitHeartbeat

INT

Heartbeat signal of the submit interpreter (counter is incremented by 1 every Submit cycle)

  • 1 … 245

Notice: During load data determination (KRC_LDDstart function block), it is possible for the heartbeat signal of the submit interpreter to be interrupted up to 400 ms.

SubmitCyc_Act

REAL

Current cycle time of the submit interpreter; unit: ms

Mean value over 1 000 ms = 1/number of cycles per second

SubmitCyc_Min

REAL

Shortest cycle time of the submit interpreter since the last broken connection; unit: ms

SubmitCyc_Max

REAL

Longest cycle time of the submit interpreter since the last broken connection; unit: ms

SubmitCyc_Avg

INT

Mean value of the cycle time of the submit interpreter during the calculation period Avg_Duration; unit: ms

ActivePosOrderID

DINT

Order ID of the KRC_Move motion command that is currently being executed

ActiveOrderIDB

DINT

Order ID of the current KRC_Move motion command in the advance run

Avg_Duration

DINT

Duration of the current calculation period for the mean value of the cycle time; unit: ms

The calculation period is restarted after a break in the connection to the submit interpreter or, at the latest, after 60 minutes.

ProconosHeartbeat

INT

Life sign of the real-time driver of mxAutomation (value is increased by 1 in each driver cycle)

ProconosCyc_Act

INT

Current cycle time of the real-time driver of mxAutomation; unit: ms

Mean value over 1 000 ms = 1/number of cycles per second

ProconosCyc_Min

INT

Shortest cycle time of the real-time driver of mxAutomation since the last broken connection; unit: ms

ProconosCyc_Max

INT

Longest cycle time of the real-time driver of mxAutomation since the last broken connection; unit: ms

ProconosCyc_Avg

INT

Mean value of the cycle time of the real-time driver of mxAutomation during the determination period Avg_Duration; unit: ms

ErrorID_RI

DINT

Robot interpreter error number

ErrorID_SI

DINT

Submit interpreter error number

ErrorID_PLC

DINT

PLC error number

ErrorID_PCOS

DINT

Error number from the real-time driver of mxAutomation

Error

BOOL

TRUE = error in function block

ErrorID

DINT

Error number