Activating and reading Automatic External signals from the robot controller
Description
The function block KRC_AutomaticExternal activates the Automatic External interface and reads the interface signals.
The function block KRC_AutoStart can be used to simplify use of KRC_AutomaticExternal.
(>>> Setting KRC_AutomaticExternal inputs automatically)
![]() | The function block requires the Automatic External mode of the robot system. Further information about this functionality is contained in the operating and programming instructions for the KUKA System Software (KSS). |
![]() | The function block may only be instanced once per axis group. In the case of multiple instancing, the signals of the most recently called function block are output. |
Inputs
|
Parameter |
Type |
Signal name (robot controller) |
Description |
|---|---|---|---|
|
AxisGroupIdx |
INT |
— |
Index of axis group
|
|
MOVE_ENABLE |
BOOL |
$MOVE_ENABLE |
TRUE = motion enable for the robot Note: This system variable is monitored by the robot controller in all operating modes. |
|
CONF_MESS |
BOOL |
$CONF_MESS |
TRUE = acknowledgement of error messages |
|
DRIVES_ON |
BOOL |
$DRIVES_ON |
TRUE = activation of the robot drives |
|
DRIVES_OFF |
BOOL |
$DRIVES_OFF |
TRUE = deactivation of the robot drives |
|
EXT_START |
BOOL |
$EXT_START |
TRUE = start or continuation of robot program execution |
|
RESET |
BOOL |
— |
Selects the mxAutomation robot program in the case of a rising edge of the signal and starts it. First, all buffered statements are aborted. |
|
ENABLE_T1 |
BOOL |
— |
TRUE = enabling of T1 mode The signal $MOVE_ENABLE is suppressed in the absence of enabling. The robot cannot be moved. |
|
ENABLE_T2 |
BOOL |
— |
TRUE = enabling of T2 mode The signal $MOVE_ENABLE is suppressed in the absence of enabling. The robot cannot be moved. |
|
ENABLE_AUT |
BOOL |
— |
TRUE = enabling of Automatic mode The signal $MOVE_ENABLE is suppressed in the absence of enabling. The robot cannot be moved. |
|
ENABLE_EXT |
BOOL |
— |
TRUE = enabling of Automatic External mode The signal $MOVE_ENABLE is suppressed in the absence of enabling. The robot cannot be moved. |
Outputs
|
Parameter |
Type |
Signal name (robot controller) |
Description |
|---|---|---|---|
|
Valid |
BOOL |
— |
TRUE = data are valid |
|
RC_RDY1 |
BOOL |
$RC_RDY1 |
TRUE = robot controller ready for program start |
|
ALARM_STOP |
BOOL |
$ALARM_STOP |
FALSE = robot stop by EMERGENCY STOP |
|
USER_SAFE |
BOOL |
$USER_SAF |
FALSE = operator safety violated |
|
PERI_RDY |
BOOL |
$PERI_RDY |
TRUE = robot drives activated |
|
ROB_CAL |
BOOL |
$ROB_CAL |
TRUE = robot axes mastered |
|
IO_ACTCONF |
BOOL |
$IO_ACTCONF |
TRUE = Automatic External interface active |
|
STOPMESS |
BOOL |
$STOPMESS |
TRUE = safety circuit interrupted (robot fault) |
|
INT_E_STOP |
BOOL |
Int. E-Stop |
TRUE = external EMERGENCY STOP FALSE = EMERGENCY STOP device pressed on the smartPAD |
|
PRO_ACT |
BOOL |
$PRO_ACT |
TRUE = process active at robot level |
|
APPL_RUN |
BOOL |
APPL_RUN |
TRUE = robot program running |
|
PRO_MOVE |
BOOL |
$PRO_MOVE |
TRUE = synchronous robot motion active |
|
ON_PATH |
BOOL |
$ON_PATH |
TRUE = robot on programmed path |
|
NEAR_POSRET |
BOOL |
$NEAR_POSRET |
TRUE = robot near most recently saved position on the programmed path (after leaving path) |
|
ROB_STOPPED |
BOOL |
$ROB_STOPPED |
TRUE = robot is at standstill |
|
T1 |
BOOL |
$T1 |
TRUE = operating mode T1 selected |
|
T2 |
BOOL |
$T2 |
TRUE = operating mode T2 selected |
|
AUT |
BOOL |
$AUT |
TRUE = operating mode Automatic selected |
|
EXT |
BOOL |
$EXT |
TRUE = operating mode Automatic External selected |