FB_CTRL_MEDIAN_FILTER

The function block specifies the median. The median is the mean value of a list of values ordered by size. This means that one half of the collected data values is smaller than the median value, the other half is larger.
The programmer must create an array "ARRAY [1..2(n+2)] OF LREAL", in which the function block can store the internal required data.
Inputs
VAR_INPUT
fIn : FLOAT;
fManSyncValue : FLOAT;
eMode : E_CTRL_MODE;
bSync : FLOAT;
bHold : BOOL;
END_VARName | Type | Description |
|---|---|---|
fIn | FLOAT | Input value of the median filter |
fManSyncValue | FLOAT | Input value to which the median filter can be set or which is output in manual mode. |
eMode | E_CTRL_MODE | With a rising edge at this input the median filter is set to the value "fManSyncValue". |
bSync | FLOAT | Input that specifies the operation mode of the function block. |
bHold | BOOL | TRUE at this input holds the internal state and thus also the output. |
Outputs
VAR_OUTPUT
fOut : FLOAT;
eState : E_CTRL_STATE;
eErrorId : E_CTRL_ERRORCODES;
bError : BOOL;
END_VARName | Type | Description |
|---|---|---|
fOut | FLOAT | Output of the median filter |
eState | E_CTRL_STATE | Status of the function block |
eErrorId | E_CTRL_ERRORCODES | Supplies the error number when the output |
bError | BOOL | Becomes TRUE, as soon as an error occurs. |
Inputs/ outputs
VAR_IN_OUT
tCtrlCycleTime : TIME := T#0ms;
tTaskCycleTime : TIME := T#0ms;
nSamplesToFilter : UINT;
pWorkArray_ADR : POINTER TO FLOAT := 0;
nWorkArray_SIZEOF : UINT := 0;
END_VARName | Type | Description |
|---|---|---|
tCtrlCycleTime | TIME | Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. |
tTaskCycleTime | TIME | Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. |
nSamplesTo | UINT | Number of values "n" used to form the median value. |
pWorkArray_ | POINTER TO FLOAT | The address of the array where the input values are temporarily stored. |
nWorkArray_ | UINT | Size of the |