FB_CTRL_RAMP_GENERATOR_EXT

This function block represents a parameterizable ramp generator. In contrast to FB_CTRL_RAMP_GENERATOR it supports E_CTRL_MODE.
Description:
This function block generates a ramp connecting the starting value fStartValue and the target value fTargetValue. The slope of the ramp (i.e. the velocity) is given in units/s by means of the fVeloPos and fVeloNeg parameters. The start value is adopted when eCTRL_MODE_RESET changes to eCTRL_MODE_ACTIVE, and calculation of the ramp begins. As long as the function block remains in eCTRL_MODE_ACTIVE the target value can be changed, and the output value changes, taking the form of a ramp as it moves from the current value to the presently active target value. The current velocity is output at fVeloOut. It is possible to use this for feed forward in the control loop.
Behavior of the output value

Inputs
VAR_INPUT
fStartValue : FLOAT;
fTargetValue : FLOAT;
fManValue : FLOAT;
bHold : BOOL;
eMode : E_CTRL_MODE;
END_VARName | Type | Description |
|---|---|---|
fStartValue | FLOAT | Start value of the ramp |
fTargetValue | FLOAT | Target value of the ramp |
fManValue | FLOAT | Input value to which the output in |
bHold | BOOL | Calculation of the ramp is halted at the current value. |
eMode | E_CTRL_MODE | Input that specifies the operation mode of the function block. |
Outputs
VAR_OUTPUT
fOut : FLOAT;
fVeloOut : FLOAT;
bValueReached : BOOL;
eState : E_CTRL_STATE;
eErrorId : E_CTRL_ERRORCODES;
bError : BOOL;
END_VARName | Type | Description |
|---|---|---|
fOut | FLOAT | Output of the ramp generator |
fVeloOut | FLOAT | Current velocity of the ramp generator |
bValueReached | BOOL | This output indicates by going TRUE that the output |
eState | E_CTRL_ | State of the function block |
eErrorId | E_CTRL_ | Supplies the error number when the output |
bError | BOOL | Becomes TRUE as soon as an error situation occurs. |
Inputs/ outputs
VAR_IN_OUT
stParams : ST_CTRL_RAMP_GENERATOR_EXT_PARAMS;
END_VAR Name | Type | Description |
|---|---|---|
stParams | ST_CTRL_RAMP_GENERATOR_EXT_ | Parameter structure of the ramp generator |
stParams consists of the following elements:
TYPE ST_CTRL_RAMP_GENERATOR_EXT_PARAMS :
STRUCT
tTaskCycleTime : TIME;
tCtrlCycleTime : TIME;
fVeloPos : FLOAT;
fVeloNeg : FLOAT;
END_STRUCT
END_TYPE Name | Type | Description |
|---|---|---|
tTaskCycleTime | TIME | Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. |
tCtrlCycleTime | TIME | Cycle time with which the function block is called. If the function block is called in every task cycle this corresponds to the task cycle time of the calling task. |
fVeloPos | FLOAT | Velocity (>0.0) in unit/s, with which the output is changed from a lower value to a higher one. |
fVeloNeg | FLOAT | Velocity (>0.0) in unit/s, with which the output is changed from a higher value to a lower one. |