FB_CTRL_LIN_INTERPOLATION

This function block performs linear interpolation to obtain values on the basis of a sampling points table.
Behavior of the output
fIn | fOut |
arrTable[1,1] := 10; | arrTable[1,2] := 7; |
arrTable[2,1] := 15; | arrTable[2,2] := 10; |
arrTable[3,1] := 21; | arrTable[3,2] := 9; |
arrTable[4,1] := 22; | arrTable[4,2] := 2; |
arrTable[5,1] := 30; | arrTable[5,2] := 3; |
arrTable[6,1] := 40; | arrTable[6,2] := 6; |

Inputs
VAR_INPUT
fIn : FLOAT;
fManValue : FLOAT;
bExtrapolate : BOOL;
eMode : E_CTRL_MODE;
END_VARName | Type | Description |
|---|---|---|
fIn | FLOAT | Input value for the interpolation function block |
fManValue | FLOAT | Input value that is output in manual mode. |
bExtrapolate | BOOL | If this input is FALSE, then the value of the last interpolation point is output if the limits of the table are exceeded. If, however, it is TRUE, then extrapolation is performed on the basis of the last two interpolation points. |
eMode | E_CTRL_MODE | Input that specifies the operation mode of the function block. |
Outputs
VAR_OUTPUT
fOut : FLOAT;
bInIsGreaterThanMaxElement : BOOL;
bInIsLessThanMinElement : BOOL;
eState : E_CTRL_STATE;
eErrorId : E_CTRL_ERRORCODES;
bError : BOOL;
END_VARName | Type | Description |
|---|---|---|
fOut | FLOAT | Table value from linear interpolation |
bInIsGreater | BOOL | A TRUE at this output indicates that the input value is greater than the largest interpolation point. |
bInIsLessThan | BOOL | A TRUE at this output indicates that the input value is smaller than the smallest interpolation point. |
eState | E_CTRL_ | State of the function block |
eErrorId | E_CTRL_ | Supplies the error number when the output |
bError | BOOL | Becomes TRUE, as soon as an error occurs. |
Inputs/ outputs
VAR_IN_OUT
stParams : ST_CTRL_LIN_INTERPOLATION_PARAMS;
END_VARName | Type | Description |
|---|---|---|
stParams | ST_CTRL_LIN_INTERPOLATION_ | Parameter structure of the interpolation element |
stParams consists of the following elements:
TYPE ST_CTRL_2POINT_PARAMS :
STRUCT
tCtrlCycleTime : TIME := T#0ms;
tTaskCycleTime : TIME := T#0ms;
pDataTable_ADR : POINTER TO FLOAT := 0;
nDataTable_SIZEOF : UINT := 0;
nDataTable_NumberOfRows : UINT := 0;
END_STRUCT
END_TYPEName | Type | Description |
|---|---|---|
tCtrlCycleTime | TIME | Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. |
tTaskCycleTime | TIME | Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. |
pDataTable_ | POINTER TO FLOAT | Address of the n x 2 array on which linear interpolation is to be carried out. |
nDataTable_ | UINT | Size of the n x 2 array |
nDataTable_ | UINT | Number of rows in the array |