FB_CTRL_DIGITAL_FILTER

This function block calculates a discrete transfer function with the structure described below. This structure allows either an FIR filter (Finite Impulse Response) or an IIR filter (Infinite Impulse Response) to be implemented. The transfer function here can be of any order, n.
The coefficients for the following transfer structure are stored in the parameter arrays:


The programmer must create the following arrays in the PLC if this function block is to be used:
aCoefficientsArray_a : ARRAY[1..nFilterOrder+1] OF FLOAT;
aCoefficientsArray_b : ARRAY[1..nFilterOrder+1] OF FLOAT;
aStDigitalFilterData : ARRAY[1..nFilterOrder] OF
ST_CTRL_DIGITAL_FILTER_DATA; The coefficients "b1" to "bn" are stored in the array aCoefficientsArray_b. This must be organized as follows:
aCoefficientsArray_b[1] := b1;
aCoefficientsArray_b[2] := b2;
…
aCoefficientsArray_b[n-1] := bn-1;
aCoefficientsArray_b[n] := bn;The coefficients "a1" to "an" are stored in the array aCoefficientsArray_a.
This must be organized as follows:
aCoefficientsArray_a[1] := xxx; (* not being evaluated *)
aCoefficientsArray_a[2] := a2;
...
aCoefficientsArray_a[n-1] := an-1;
aCoefficientsArray_a[n] := an;The internal data required by the function block is stored in the array aStDigitalFilterData. This data must never be modified from within the PLC program. This procedure is also illustrated in the sample program listed below.
Inputs
VAR_INPUT
fIn : FLOAT;
fManValue : FLOAT;
eMode : E_CTRL_MODE;
END_VARName | Type | Description |
|---|---|---|
fIn | FLOAT | Input of the digital filter |
fManValue | FLOAT | Input whose value is present at the output in manual mode. |
eMode | E_CTRL_MODE | Input that specifies the operation mode of the function block. |
Outputs
VAR_OUTPUT
fOut : FLOAT;
eState : E_CTRL_STATE;
bError : BOOL;
eErrorId : E_CTRL_ERRORCODES;
END_VARName | Type | Description |
|---|---|---|
fOut | FLOAT | Output of the digital filter |
eState | E_CTRL_STATE | State of the function block |
bError | BOOL | Becomes TRUE, as soon as an error occurs. |
eErrorId | E_CTRL_ERRORCODES | Supplies the error number when the output |
Inputs/ outputs
VAR_IN_OUT
stParams : ST_CTRL_DIGITAL_FILTER_PARAMS;
END_VARName | Type | Description |
|---|---|---|
stParams | ST_CTRL_ | Parameter structure of the function block |
stParams consists of the following elements:
TYPE
ST_CTRL_DIGITAL_FILTER_PARAMS :
STRUCT
tTaskCycleTime : TIME;
tCtrlCycleTime : TIME := T#0ms;
nFilterOrder : USINT;
pCoefficientsArray_a_ADR : POINTER TO FLOAT := 0;
nCoefficientsArray_a_SIZEOF : UINT;
pCoefficientsArray_b_ADR : POINTER TO FLOAT := 0;
nCoefficientsArray_b_SIZEOF : UINT;
pDigitalFilterData_ADR : POINTER TO ST_CTRL_DIGITAL_FILTER_DATA;
nDigitalFilterData_SIZEOF : UINT;
END_STRUCT
END_TYPEName | Type | Description |
|---|---|---|
tTaskCycleTime | TIME | Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. |
tCtrlCycleTime | TIME | Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. |
nFilterOrder | USINT | Order of the digital filter [0... ] |
pCoefficientsArray_a_ADR | POINTER TO FLOAT | Address of the array containing the a coefficients |
nCoefficientsArray_a_SIZEOF | UINT | Size of the array containing the a coefficients, in bytes |
pCoefficientsArray_b_ADR | POINTER TO FLOAT | Address of the array containing the b coefficients |
nCoefficientsArray_b_SIZEOF | UINT | Size of the array containing the b coefficients, in bytes |
pDigitalFilterData_ADR | POINTER TO ST_CTRL_ | Address of the data array |
nDigitalFilterData_SIZEOF | UINT | Size of the data array in bytes |
TYPE
ST_CTRL_DIGITAL_FILTER_DATA
STRUCT
Internal structure. This must not be written to.
END_STRUCT
END_TYPESample:
PROGRAM PRG_DIGITAL_FILTER_TEST
VAR
fbDigitalFilter : FB_CTRL_DIGITAL_FILTER;
aCoefficientsArray_a : ARRAY[1..3] OF FLOAT;
aCoefficientsArray_b : ARRAY[1..3] OF FLOAT;
aStDigitalFilterData : ARRAY[1..2] OF ST_CTRL_DIGITAL_FILTER_DATA;
eMode : E_CTRL_MODE;
stParams : ST_CTRL_DIGITAL_FILTER_PARAMS;
eErrorId : E_CTRL_ERRORCODES;
bError : BOOL;
fIn : FLOAT := 0;
fOut : FLOAT;
bInit : BOOL := TRUE;
END_VAR
IF bInit THEN
aCoefficientsArray_a[1] := 0.0; (* not used *)
aCoefficientsArray_a[2] := 0.2;
aCoefficientsArray_a[3] := 0.1;
aCoefficientsArray_b[1] := 0.6;
aCoefficientsArray_b[2] := 0.4;
aCoefficientsArray_b[3] := 0.2;
stParams.tTaskCycleTime := T#2ms;
stParams.tCtrlCycleTime := T#2ms;
stParams.nFilterOrder := 2;
eMode := eCTRL_MODE_ACTIVE;
bInit := FALSE;
END_IF
stParams.pCoefficientsArray_a_ADR := ADR(aCoefficientsArray_a);
stParams.nCoefficientsArray_a_SIZEOF := SIZEOF(aCoefficientsArray_a);
stParams.pCoefficientsArray_b_ADR := ADR(aCoefficientsArray_b);
stParams.nCoefficientsArray_b_SIZEOF := SIZEOF(aCoefficientsArray_b);
stParams.pDigitalFilterData_ADR := ADR(astDigitalFilterData);
stParams.nDigitalFilterData_SIZEOF := SIZEOF(aStDigitalFilterData);
fbDigitalFilter ( fIn := fIn,
eMode := eMode,
stParams := stParams,
fOut => fOut,
eErrorId => eErrorId,
bError => bError);