FB_CTRL_ACTUAL_VALUE_FILTER
The function block allows a measured input value to be checked for plausibility and filtered.
Behavior of the output

This function block allows a plausibility check to be carried out on a measured input value. If the difference between two sampling values in sequence (measurements) is larger than the specified window, fDeltaMax, then the current input value is suppressed for a maximum of three cycles. During this time the output value is extrapolated from the previous input values. If the specified window is exceeded for more than three cycles, the output will again follow the input value. The behavior of the output is illustrated in the diagram above.
Inputs
VAR_INPUT
fIn : FLOAT;
fManValue : FLOAT;
eMode : E_CTRL_MODE;
END_VARName | Type | Description |
|---|---|---|
fIn | FLOAT | Input value of the filter |
fManValue | FLOAT | Input value that is output in manual mode. |
eMode | E_CTRL_MODE | Input that specifies the operation mode of the function block. |
Outputs
VAR_OUTPUT
fOut : FLOAT;
eState : E_CTRL_STATE;
eErrorId : E_CTRL_ERRORCODES;
bError : BOOL;
END_VARName | Type | Description |
|---|---|---|
fOut | FLOAT | Output of the function block |
eState | E_CTRL_ | State of the function block |
eErrorId | E_CTRL_ | Supplies the error number when the output |
bError | BOOL | Becomes TRUE, as soon as an error occurs. |
Inputs/ outputs
VAR_IN_OUT
stParams : ST_CTRL_ACTUAL_VALUE_FILTER_PARAMS;
END_VARName | Type | Description |
|---|---|---|
stParams | ST_CTRL_ACTUAL_VALUE_FILTER_ | Parameter structure of the actual value filter element |
stParams consists of the following elements:
TYPE
ST_CTRL_ACTUAL_VALUE_FILTER_PARAMS:
STRUCT
tCtrlCycleTime : TIME := T#0ms;
tTaskCycleTime : TIME := T#0ms;
fDeltaMax : FLOAT;
END_STRUCT
END_TYPEName | Type | Description |
|---|---|---|
tCtrlCycleTime | TIME | Cycle time with which the control loop is processed. This must be greater than or equal to the TaskCycleTime. The function block uses this input value to calculate internally whether the state and the output values have to be updated in the current cycle. |
tTaskCycleTime | TIME | Cycle time with which the function block is called. If the function block is called in every cycle this corresponds to the task cycle time of the calling task. |
fDeltaMax | FLOAT | Maximum difference between two input values in sequence. See description above. |