FB_ALY_Demultiplexer
The demultiplexer selects an output channel based on the input value. For this purpose, the input value is interpreted as an integer. This value corresponds to the output channel. If the value is outside the configured number of channels, the output channel is set to 0.
Syntax
Definition:
FUNCTION_BLOCK FB_ALY_Demultiplexer
VAR_OUTPUT
ipResultMessage: Tc3_EventLogger.I_TcMessage;
bError: BOOL;
bNewResult: BOOL;
bConfigured: BOOL;
bSwitched: BOOL;
nCurrentChannel: UDINT;
nCount: ULINT;
fbTimeLastEvent: FB_ALY_DateTime;
END_VAR
Outputs
Name | Type | Description |
|---|---|---|
ipResultMessage | Contains more detailed information on the current return value. This special interface pointer is internally secured so that it is always valid/assigned. | |
bError | BOOL | This output is |
bNewResult | BOOL | When a new result has been calculated, the output is |
bConfigured | BOOL | Displays |
bSwitched | BOOL |
|
nCurrentChannel | UDINT | Indicates the number of the selected channel. The value is 0 if the selected channel is outside the configured channels. |
nCount | ULINT | Starts with 1 for the channel selected at the start of the analysis and increments each time another channel is selected. |
fbTimeLastEvent | FB_ALY_DateTime | Timestamp of the last channel change. |
Methods
Name | Definition location | Description |
|---|---|---|
Call() | Local | Method for calculating the outputs for a specific configuration. |
GetResults() | Local | Getting the result array without adding new values |
FB_init() | Local | Initializes the number of output channels. |
Reset() | Local | Resets all internal states or the calculations performed so far. |
SetChannelValue() | Local | Method for passing channel-specific values to the algorithm. |
Sample
VAR
fbDemultiplexer : FB_ALY_Demultiplexer(nNumChannels := 3);
fbSystemTime : FB_ALY_GetSystemTime;
nInput : INT := 1;
aResults : ARRAY[0..3] OF BOOL;
END_VAR// Get current system time
fbSystemTime.Call();
// Call algorithm
fbDemultiplexer.SetChannelValue(nInput);
fbDemultiplexer.Call(fbSystemTime.tSystemTime, ADR(aResults), SIZEOF(aResults));Requirements
Development environment | Target platform | Plc libraries to include |
|---|---|---|
TwinCAT v3.1.4024.0 | PC or CX (x64, x86) | Tc3_Analytics |