SA0028: Overlapping memory areas
![]() | This rule can only be checked using the Command 'Run static analysis' command, not using the “Check all objects” option. |
Function | Determines the points due to which two or more variables occupy the same storage space. |
Reason | If two variables occupy the same storage space, the code may behave very unexpectedly. This must be avoided in all cases. If the use of a value in different interpretations is unavoidable, for example once as DINT and once as REAL, you should define a UNION. Also, via a pointer you can access a value typed otherwise without converting the value. |
Importance | High |
Sample:
In the following sample both variables use byte 21, i.e. the memory areas of the variables overlap.
PROGRAM MAIN
VAR
nVar1 AT%QB21 : INT; // => SA0028
nVar2 AT%QD5 : DWORD; // => SA0028
END_VAR