AX2xxx Drive - Status and Error Codes
At AX2xxx-B200 drives, the variables DriveError,DriveState and Status are added via Variable I/O Data.
At AX2xxx-B900 drives, the I/O variables DriveState2 and DriveState3 appear by default under "Inputs", but the DriveError variables are to be added manually. Please find additional info under: AX2xxx Drive Tab - Inputs.
These input variables can be used for diagnosis purposes (e.g. if they are linked to a TwinCAT PLC process image, they can be evaluated inside the TwinCAT PLC run-time system).
In any case, the error and warning codes are displayed on the 7-segment display of the AX2xxxx drive (see column: "AX2xxx Display").
Variable | Data Type | Value | AX2xxx Display | Designation |
|---|---|---|---|---|
DriveError
(can also be linked byte-wise with help of the variables DriveError0,DriveError1,DriveError2 andDriveError3)
The equivalent ASCII command is: ERRCODE * resp. ERRCODE | UINT32 | 0x00000001 | F01 | Error heat sink temperature |
0x00000002 | F02 | Error overvoltage | ||
0x00000004 | F03 | Error position controller (drive) | ||
0x00000008 | F04 | Feedback error (Resolver) | ||
0x00000010 | F05 | Error undervoltage | ||
0x00000020 | F06 | Error motor temperature | ||
0x00000040 | F07 | Internal supply voltage | ||
0x00000080 | F08 | Speed error | ||
0x00000100 | F09 | Error EEPROM | ||
0x00000200 | F10 | Reserved | ||
0x00000400 | F11 | Brake error | ||
0x00000800 | F12 | Reserved | ||
0x00001000 | F13 | Error ambient temperature | ||
0x00002000 | F14 | Amplifier error | ||
0x00004000 | F15 | Error I2T exceeded | ||
0x00008000 | F16 | Supply voltage not correct | ||
0x00010000 | F17 | Error A/D Converter is set if offsets of drive current values are too high during startup. | ||
0x00020000 | F18 | Ballast transistor error with bad ballast transistor respectively preselection of "external ballast resistor" in combination with connected internal ballast resistor, this error is going to be set. | ||
0x00040000 | F19 | Error missing phase. at PMODE=2. | ||
0x00080000 | F20 | Slot Error This error condition is generated if there are problems with present slot expansion card (e.g. AX2xxx-B200). This error message is depending on the used expansion slot card type. It usually points to a faulty interface hardware. | ||
0x00100000 | F21 | PROFIBUS Handling Error This error can only happen in combination with the use of a Profibus expansion card (part no.: AX2xxx-B310). | ||
0x00200000 | F22 | Drive circuits are grounded to earth potential (PE) | ||
0x00400000 | F23 | Error in CAN communication This error message BUSOFF is generated directly by level 2 of the internal CAN controller. | ||
0x00800000 | F24 | Error Watchdog This error is displayed, if the telegram update time exceeded the value set in EXTWD. | ||
0x01000000 | F25 | Error in commutation At this error message, the motor has a commutation problem (uncontrolled motor behavior). The commutation treshold value can be changed under VCOMM, the unit is RPM (rounds per minute). | ||
0x02000000 | F26 | Error in calibration (hardware limit switch) is defined by REFLS. | ||
0x04000000 | F27 | Error AS-Option is set, if amplifier was enabled during activation of the optional starting inhibiting circuit (part no.: AX20xx-yyyy-0001). | ||
0x08000000 | F28 | Error "external position setpoint offset" External position setpoint offset beyond limit. | ||
0x10000000 | F29 | SERCOS error | ||
0x20000000 | F30 | SERCOS emergency stop timeout | ||
0x40000000 | F31 | Reserved | ||
0x80000000 | F32 | System error shows an internal error. This error is generated at drive startup if system check didn't succeed during initialization. For further information, see detailed AX2000 / AX2500 manuals supplied with drive. | ||
DriveState
(can also be linked byte-wise with help of the variables DriveState0,DriveState1,DriveState2 and DriveState3 )
The equivalent ASCII command is: | UINT32 | 0x00000001 | n01 | Warning I2T- threshold value exceeded |
0x00000002 | n02 | Warning ballast circuit is set, if the current regen circuit exceeds the threshold value set under PBALMAX. The warning is cleared as soon as the value goes below PBALMAX. | ||
0x00000004 | n03 | Warning lag-distance exceeded is set, as soon as the distance between the set position and the position controller trajectory exceed the set value PEMAX. It can be deleted with the command CLRFAULT. | ||
0x00000008 | n04 | Watchdog warning is set, if the fieldbus watchdog time EXTWD was exceeded. | ||
0x00000010 | n05 | Warning: At least one supplied phase is missing is displayed, if not all three phases of supply voltage are supplied. | ||
0x00000020 | n06 | Warning: Software limit switch 1 below minimum is set, if the value of the software limit switch 1is below SWE1. In addition, the warning is set, if a motion task was started with a target position below the value specified in drive object SWE1. The warning message is cleared as soon as SWE1 is exceeded and a positive speed setpoint value is passed over (means, when a start command with valid position values is supplied). | ||
0x00000040 | n07 | Warning: Software limit switch 2 beyond maximum is set, if the value of the software limit switch 2 is beyond SWE2. In addition, the warning is set, if a motion task was started with a target position beyond the value specified in drive object SWE2. The warning message is cleared as soon as SWE2 stays below and a negative speed setpoint value is passed over (means, when a start command with valid position values is supplied). | ||
0x00000080 | n08 | Warning: Wrong start command is set if it was tried to start an undefined (missing checksum) motion task. The warning is cleared automatically if a valid start command is supplied. | ||
0x00000100 | n09 | Warning: Reference point (calibration) not set is set if a motion task was initiated without a calibration/homing done before. | ||
0x00000200 | n10 | Warning: PSTOP activated is set if hardware limit switch PSTOP (stop switch in positive direction) is activated. Warning is cleared as soon as the limit switch is released again. | ||
0x00000400 | n11 | Warning: NSTOP activated is set if hardware limit switch NSTOP (stop switch in negative direction) is activated. Warning is cleared as soon as the limit switch is released again. | ||
0x00000800 | n12 | Warning: Default motor data loaded | ||
0x00001000 | n13 | Slot warning (I/O card) | ||
0x00002000 | n14 | Recognition of MPHASE (FBTYPE=7) | ||
0x00004000 | n15 | Warning: Wrong VCT-Entry selected (table error)
| ||
0x00008000 | n16 | Warning active n17 .. n31 is set, if one or several warnings in the range between n17.. n31 are active | ||
0x00010000 |
| Motion task active | ||
0x00020000 |
| Reference point is set. | ||
0x00040000 |
| Home switch | ||
0x00080000 |
| In-Position When several motion tasks are tied together, only the last motion task enables this bit. | ||
0x00100000 |
| Position latch occurred (positive edge) Is cleared, if the lachted position was read (LATCH16 / LATCH32 ).
| ||
0x00200000 |
| Position register 0 | ||
0x00400000 |
| Position register 1 | ||
0x00800000 |
| Position register 2 | ||
0x01000000 |
| Position register 3 | ||
0x02000000 |
| Position register 4 | ||
0x04000000 |
| Initialization phase finished | ||
0x08000000 |
| Position register 5 | ||
0x10000000 |
| Motor stand still message | ||
0x20000000 |
| Safety relays selected | ||
0x40000000 |
| Output stage enabled | ||
0x80000000 |
| Drive is in error condition The bit is cleared if the drive is reset or the command CLRFAULT is send.
| ||
|
|
| ||
|
|
| ||
|
|
| ||
|
|
| ||
State | UINT8 | 0x01 |
| Command error |
0x02 |
| Error in input data | ||
0x04 |
| Error in output data | ||
0x08 |
| Timeout | ||
0x10 |
| Error K-Bus Reset |