Beckhoff FC510x Hardware Description

The FC510x is a CANopen Master card with one (FC5101) or two channels (FC5102). The CAN transceivers are galvanically isolated.

CAN Terminating Resistor

On the card there are CAN terminating resistors (120 Ohms). These can be activated with a jumper (up to hardware version 3) or with a switch (from hardware version 4) close to the CAN connectors.

The Flash Disk Socket is currently not in use.

Beckhoff FC510x Hardware Description 1:

Pin assignment

The CAN bus line is connected via 9-pin D-Sub sockets with the following pin assignment.

Pin

Assignment

2

CAN low (CAN-)

3

CAN Ground (internally connected to pin 6)

5

Shield

6

CAN Ground (internally connected to pin 3)

7

CAN high (CAN+)

The unlisted pins are not connected.

Beckhoff FC510x Hardware Description 2:

Auxiliary voltage

An auxiliary voltage of up to 30 VDC may be connected to pin 9. Some CAN devices use this to supply the transceiver.

Beckhoff FC510x Hardware Description 3:

LED Behavior

The red ERROR LED and the green RUN help to quickly diagnose the status of the card:

Error LED (red)

Run LED (green)

Description

off

off

TwinCAT has been stopped

off

on

All configured bus nodes are error free (Box State=0), TwinCAT Task or Process is running.

off

blinking with 2 Hz

The Task, whose process data is linked to the card, is not running.
All configured bus nodes have been found and are error free (Box State=0)

blinking with 2Hz

on

At least one box state is unequal zero (e.g. node not found, wrong configuration, node in error), TwinCAT Task is running

blinking with 2 Hz

off

At least one box state is unequal zero (e.g. node not found, wrong configuration, node in error), TwinCAT Task is not running

on

off

TwinCAT is running, CAN Controller is "Bus OFF". Physical CAN problem. Possible reasons: e.g. terminating resistor missing, bus too long, wrong baud rate, node address configured twice, short circuit, wiring error.

Restart is necessary

blinking with 20Hz

blinking with 20Hz

Configuration Upload is under way

blinking with 20Hz

off

card is in STOP mode