St_StateEV
Information on the status of the EV.
TYPE St_StateEV :
STRUCT
bFlow_with_closed_valve : BOOL;
bAir_bubbles : BOOL;
bFlow_not_reached : BOOL;
bPower_not_realized : BOOL;
bGear_disengaged : BOOL;
END_STRUCT
END_TYPE
bFlow_with_closed_valve: Flow with the valve closed. check valve.
bAir_bubbles: Too many air bubbles (system inadequately vented). Flow measurement is no longer accurate. EV will change from flow control to position control.
bFlow_not_reached: Flow is not reached, although the control valve is fully open. Check hydraulic, turn on pump or increase pump pressure.
bPower_not_realized: Performance is not achieved. The EV can next to the position control and flow control directly conduct a performance. Primary side gives too little flow or dT.
bGear_disengaged: Gear disengagement active. Manual adjustment on site possible. In other MP drives, this information can be read with MP_Get_State.