FB_ASI_Addressing
VAR_IN_OUT
VAR_IN_OUT
stParameterBuffer: ST_ParameterBuffer;
END_VAR
stParameterBuffer: Data buffer for background communication
VAR_INPUT
VAR_INPUT
iOldAddress : BYTE; (*old address*)
iNewAddress : BYTE; (*new address*)
bStart : BOOL; (*START*)
END_VAR
iOldAddress: old address of the slave to be addressed (new slaves have address 0)
iNewAddress: new address of the slave to be addressed
bStart : Addressing is carried out via a rising edge of this boolean input
VAR_OUTPUT
VAR_OUTPUT
bBusy : BOOL;
bErr : BOOL;
iErrornumber : DWORD; (*errorcode of ASI-Master*)
END_VAR
bBUSY: This output remains TRUE until the block has executed a command. While Busy = TRUE, no new command will be accepted at the inputs. Please note that it is not the execution of the service but its acceptance whose time is monitored.
bErr: This output shows the error status
iErrornumber: Contains the command-specific error code of the most recently executed command. Is reset to 0 by the execution of an instruction at the inputs.
Requirements
Development environment | Target system type | IO Hardware | PLC libraries to include |
|---|---|---|---|
TwinCAT Version >= 2.8.0 Build > 739 | PC (i386) | ASI master terminal | TcIoFunctions.Lib ( Standard.Lib; TcBase.Lib; TcSystem.Lib; TcUtilities.Lib are included automatically ) |