F_Byte_to_TurnSwitch : STREnOceanTurnSwitch
This function converts a byte raw value into a bool array, which is present as a data structure.
VAR_INPUT
byData : BYTE;
byData: Raw data.
F_Byte_To_TurnSwitch: data structure (AUTO, 0, I, II, III).
The values are interpreted as follows:
210. .255: f_Byte_to_TurnSwitch.bStageAuto := TRUE;
190 ..209: f_Byte_to_TurnSwitch.bStage_0 := TRUE;
165. .189: f_Byte_to_TurnSwitch.bStage_1 := TRUE;
145. .164: f_Byte_to_TurnSwitch.bStage_2 := TRUE;
0.. 144: f_Byte_to_TurnSwitch.bStage_3 := TRUE;