OnInitData

Abstract event method for initializing the next record to be read. The derived implementation provides all the information needed for ADS read access and uses the return value to indicate whether another record should be processed.
Syntax
METHOD PROTECTED ABSTRACT OnInitData : BOOL
VAR_INPUT
nDataSet : UINT;
END_VAR
VAR_OUTPUT
sSource_NetID : T_AmsNetId;
sSource_Symbol : T_MaxString;
pTarget_Data : PVOID;
nTarget_Size : UDINT;
bParam : BOOL;
nParam : INT;
END_VAR
Inputs
|
Name |
Type |
Description |
|---|---|---|
|
nDataSet |
UINT |
Counter for the data record to be initialized. |
Outputs
|
Name |
Type |
Description |
|---|---|---|
|
sSource_NetID |
AMS Net ID of the ADS source. | |
|
sSource_Symbol |
Symbol name of the ADS value to be read. | |
|
pTarget_Data |
PVOID |
The destination address to which the read data is written. |
|
nTarget_Size |
UDINT |
Size of the destination buffer in bytes. |
|
bParam |
BOOL |
An optional parameter that is passed on to succeeding event methods. |
|
nParam |
INT |
An optional numeric parameter that is passed to succeeding event methods. |