E_BA_AlarmMode
Describes the Alarm mode of Event-enabled objects.
Syntax
{attribute 'qualified_only'}
TYPE E_BA_AlarmMode :
(
Undefined := 0,
UserDefined := 1,
eSimple := 2,
eStandard := 3,
eExtended := 4
) BYTE;
END_TYPE
Name | Description |
|---|---|
|
|
Undefined | No function. |
UserDefined | User-defined pattern bit combination. According to BACnet, any combination of the AcknowledgeRequired bits (0 or 1) can be used. The EventNotification can be configured either as an event or as an alarm. Acknowledgment: For each state transition (TO-OFFNORMAL, TO-NORMAL, and TO-FAULT), you can specify whether acknowledgment is required or not. |
eSimple | Neither incoming nor outgoing alarms need to be acknowledged. The alarm indication disappears automatically when the alarm ends. |
eStandard | Only incoming, but not outgoing alarms need to be acknowledged. Acknowledgment but no reset of the alarm is required. The alarm indication disappears when the past alarm is acknowledged. |
eExtended | Both the acknowledgment and the reset of the alarm are required. The alarm indication disappears when the past alarm is acknowledged and reset. Depending on the acknowledgment mode, a simple acknowledgment may be sufficient to trigger the reset. |
Bit combinations for UserDefined:
Flag | TO-OFFNORMAL | TO-FAULT | TO-NORMAL |
|---|---|---|---|
ACK_REQUIRED | x | x | x |
EVENT_ENABLED | x | x | x |