E_BA_NoEnableSeqCtrl
If during the running process the active sequence controller loses its operational readiness, then the enumeration E_BA_NoEnableSeqCtrl defines the procedure to find a new, active sequence controller.
E_BA_NoEnableSeqCtrl is used in FB_BA_SequenceLinkBase.
Syntax
TYPE E_BA_NoEnableSeqCtrl :
(
eFirstSeqNum := 1,
eLastSeqNum := 2,
eFirstActionDirect := 3,
eLastActionReverse := 4,
eNextSeqCtrl := 5,
ePreviousSeqCtrl := 6,
eNextAction := 7
) UDINT;
END_TYPEName | Description |
|---|---|
eFirstSeqNum | The first sequence controller that is ready to operate becomes the new, active sequence controller. |
eLastSeqNum | The last sequence controller that is operational becomes the new, active sequence controller. |
eFirstActionDirect | The first operational sequence controller with the E_BA_Action.eDirect control direction will be the new active sequence controller. If none is found, then E_BA_NoEnableSeqCtrl.eLastSeqNum is implemented. |
eLastActionReverse | The last sequence controller that is operational and has the control direction E_BA_Action.eReverse becomes the new, active sequence controller. If none is found, then E_BA_NoEnableSeqCtrl.eFirstSeqNum is implemented. |
eNextSeqCtrl | The next operational sequence controller after the last active one becomes the new active sequence controller (after 5, 6 or higher would follow). If none is found, then E_BA_NoEnableSeqCtrl.eLastSeqNum is implemented. |
ePreviousSeqCtrl | The previous operational sequence controller before the last active one becomes the new active sequence controller (after 5, 4 or lower would follow). If none is found, then E_BA_NoEnableSeqCtrl.eFirstSeqNum is implemented. |
eNextAction | A new, active sequence controller is defined based on the control direction of the sequence controller that is no longer active. Control direction eActn = E_BA_Action.eDirect (Cooling): The next sequence controller that is ready to operate and has the control direction E_BA_Action.eDirect becomes the new active controller in the sequence control (after 5, 6, or higher would follow). If none is found, then E_BA_NoEnableSeqCtrl.eLastSeqNum is implemented. Control direction eActn = E_BA_Action.eReverse (Heating): The previous, operational sequence controller with the direction of action E_BA_Action.eReverse becomes the new, active one in the sequence control (after 5, 4, or lower would follow). If none is found, then E_BA_NoEnableSeqCtrl.eFirstSeqNum is implemented. |