The function block FB_BA_RFTrig is used to detect a rising or falling edge on a boolean variable.
Syntax
FUNCTION_BLOCK FB_BA_RFTrig
VAR_INPUT
bValue :BOOL;
END_VAR
VAR_OUTPUT
Q :BOOL;
Qr :BOOL;
Qf :BOOL;
END_VAR
Outputs
Name | Type | Description |
|---|---|---|
Q | BOOL | TRUE for one cycle if a rising or falling edge was detected at bValue. |
Qr | BOOL | TRUE for one cycle if a rising edge was detected at bValue (monitored value changes from FALSE to TRUE). |
Qf | BOOL | TRUE for one cycle if a falling edge was detected at bValue (monitored value changes from TRUE to FALSE). |
Requirements
Development environment | Required PLC library |
|---|---|
TwinCAT 3.1 4024.35 | Tc3_BA2_Common from V2.1.20.0 |
Inputs