FB_ScopeServerControl
[This documentation is preliminary and subject to modifications]
The function block "FB_ScopeServerControl" enables the PLC to collect data for subsequent display with TwinCAT Scope 2.
VAR_INPUT
VAR_INPUT
sNetId : T_AmsNetId;
eReqState : E_ScopeServerState := SCOPE_SERVER_IDLE;
sConfigFile : STRING;
sSaveFile : STRING;
tTimeout : TIME := DEFAULT_ADS_TIMEOUT;
END_VAR
sNetId: This parameter can be used to specify a string containing the network address of the TwinCAT target system (type: T_AmsNetID). For the local computer this string may be empty.
eReqState:: Requested scope server status (type: E_ScopeServerState).
sConfigFile:: Full path with the name of the configuration file (e.g.: 'C:\TwinCAT\TwinCATScope2\First.sv2' ).
sSaveFile: Full path with the name of data file (e.g: 'C:\TwinCAT\TwinCATScope2\First.svd').
tTimeout:: Maximum permitted time for the internal ADS commands
VAR_OUTPUT
VAR_OUTPUT
bBusy : BOOL;
bDone : BOOL
bError : BOOL;
nErrorId : UDINT;
END_VAR
bBusy: When the function block is activated this output is set. It remains set until a feedback is received.
bDone: Is set if the requested status was activated.
bError: In the event of an error during the command transfer, this output is set once the bBusy output has been reset.
nErrorId: Shows the error number if the error output bError is set. As a rule this can be an ADS error number or a specific error code of this library.
![]() | Only one target system is permitted for the configuration file (*.sv2). |
State diagram:
*) to reset State Change is always possible
This state diagram shows the possible transitions for eReqState. If there is an other state change requested bError will be set.
TYPE E_ScopeServerState
TYPE E_ScopeServerState
(
SCOPE_SERVER_IDLE,
SCOPE_SERVER_CONNECT,
SCOPE_SERVER_START,
SCOPE_SERVER_STOP,
SCOPE_SERVER_SAVE,
SCOPE_SERVER_DISCONNECT,
SCOPE_SERVER_RESET
);
Example:
Declaration part:
FUNCTION_BLOCK FB_ScopeServerSample
VAR_INPUT
bExternalTriggerEvent: BOOL := FALSE;
END_VAR
VAR_OUTPUT
END_VARVAR
fbScopeServerControl: FB_ScopeServerControl;
eReqState: E_ScopeServerState := SCOPE_SERVER_IDLE;
bBusy: BOOL := FALSE;
bDone: BOOL := FALSE;
bError: BOOL := FALSE;
nErrorId: UDINT := 0;
fbTimer: TON;
bTriggerTimer: BOOL := FALSE;
nState: UDINT := 0;
END_VAR
Implementation of the FB_ScopeServerSample
CASE nState OF
0:
eReqState := SCOPE_SERVER_START;
nState := 10;
10:
IF fbScopeServerControl.bDone AND bExternalTriggerEvent
THEN
bTriggerTimer := TRUE;
nState := 20;
END_IF
20:
IF fbTimer.Q THEN
eReqState := SCOPE_SERVER_SAVE;
bTriggerTimer := FALSE;
nState := 30;
END_IF
30:
IF fbScopeServerControl.bDone THEN
eReqState := SCOPE_SERVER_DISCONNECT;
END_IF
END_CASE
fbTimer(IN:=bTriggerTimer, PT:=t#10s);
fbScopeServerControl( sNetId:= '',
eReqState:= eReqState,
sConfigFile:= 'C:\twinCat\scope\test.sv2',
sSaveFile:= 'C:\twinCat\scope\test.svd',
tTimeout:= t#5s,
bBusy=>bBusy,
bDone=>bDone,
bError=>bError,
nErrorId=>nErrorId);
This example demonstrates a long-term recording with the Scope Server.
The existing configuration (Test.sv2) is loaded for this purpose. In this example Test.sv2 was stored in order to run in the ring buffer. Data logging will not finish until FB_ScopeServerControl becomes active. If an internal trigger event (e.g. an error event) occurs, a timer is started, and 10 seconds later the data are saved in Test.svd. In this way the data file contains information from before and after the trigger event.
Requirements
Development environment |
Target platform |
PLC libraries to be integrated (category group) |
---|---|---|
TwinCAT v3.1.0 |
PC or CX (x86, x64, ARM) |
Tc2_Utilities (System) |