FB_CXReadKBusError

The function block enables further information to be read out about a K-bus error in order to obtain a more precise error image and to enable better diagnosis.
The prerequisite for this is that you use the K-bus terminals directly on your CX.
Example: If you are using the K-bus extension and the cable of the K-bus extension is disconnected, then you will see a K-bus interruption as nErrorCode = 4 and the position where the K-bus has been interrupted as nErrorArgument = Position.
Further information on possible K-bus errors using the CX7000 as an example:
https://infosys.beckhoff.com/content/1033/cx7000/9948355595.html?id=6787792405096234356
Inputs
FUNCTION_BLOCK FB_ CXReadKBusError
VAR_INPUT
bEnable : BOOL;
END_VARName | Type | Description |
|---|---|---|
bEnable | BOOL | Link this variable to bit 0 of the K-bus state to activate the read process automatically in case of a K-bus error. The K-bus State is a Word variable. To mask out bit 0 of your linked variables, you can use |
Outputs
VAR_OUTPUT
bBusy : BOOL;
bError : BOOL;
nErrorID : UDINT;
bKBusError : BOOL;
nKBusErrorCode : UINT;
nKBusErrorArgument : UINT;
END_VARName | Type | Description |
|---|---|---|
bBusy | BOOL | The function block is active and working. |
bError | BOOL | The function block has an error. |
nErrorID | UDINT | ADS error code |
bKBusError | BOOL | The K-bus has an error. Further information is available at the outputs |
nKBusErrorCode | UINT | K-bus error code |
nKBusErrorArgument | UINT | K-bus error argument |
Once the error has been corrected, the K-bus can be restarted via the function block IOF_DeviceReset (from the PLC library Tc2_IoFunctions).
Development environment | Target platform | PLC libraries to include |
|---|---|---|
TwinCAT v3.1.4024.22 | CX (x86, x64, Arm®) | Tc2_SystemCX (System) >= 3.4.7.0 |