Example with AdsWrite function block
The example demonstrates the use of the ADSWRITE function block in an ADS Client application.
The complete sources of the ADS Client application can be unpacked here: AdsWriteReqClientExample.zip
Declaration Part
PROGRAM MAIN
VAR
fbWriteReq : ADSWRITE := ( NETID := '', PORT := 851, TMOUT := DEFAULT_ADS_TIMEOUT );
bWrite : BOOL;(* Rising edge at this variable starts command execution *)
nState : BYTE;
bBusy : BOOL;
bError : BOOL;
nErrID : UDINT;
arrInt : ARRAY[0..9] OF INT;(* Server data to be written *)
i : INT;
END_VARImplementation
FOR i:=0 TO 9 BY 1 DO (* modify/simulate new data *)
arrInt[i] := arrInt[i] + 1;
END_FOR
CASE nState OF
0:
IF bWrite THEN
bWrite := FALSE;
bBusy := TRUE;
bError := FALSE;
nErrID := 0;
fbWriteReq( WRITE := FALSE );
fbWriteReq( IDXGRP := 16#80000005, IDXOFFS := 7,
LEN := SIZEOF( arrInt ), SRCADDR := ADR( arrInt ),
WRITE := TRUE );
nState := 1;
END_IF
1:
fbWriteReq( WRITE := FALSE, BUSY=>bBusy, ERR=>bError, ERRID=>nErrID );
IF NOT bBusy THEN
IF NOT bError THEN
nState := 0;(* Success *)
ELSE
nState := 100;(* Error *)
END_IF
END_IF
100:(* TODO::Implement error handler *)
nState := 0;
END_CASE